Delaware fire alarm Annual Certificate of Inspection: how to fill and file it
General information, not an official State Fire Marshal page. Last checked 2026-11-26 against the sources linked below. The licensed company is responsible for its own filings.
Short answer
- What it is: a one-page state form that a licensed company sends to the Office of the State Fire Marshal after the annual inspection of a fire protection system. It verifies that the inspection, testing or maintenance met the Delaware State Fire Prevention Regulations, and it lists any deficiencies with the corrective action taken (Regulation 703, Chapter 4, § 8.1).
- Who files it: the licensed company that inspects, tests or maintains the system, not the building owner (§ 8.1). Certificates are not required for one- and two-family dwellings (§ 8.1, exception).
- How many: one certificate per fire alarm signaling system. A separate system is a control unit with its initiating circuits, signaling circuits and primary and secondary power, designed to work as one system (§ 8.2).
- Deadline: within 30 days of the annual inspection (Chapter 4, § 8.4; Chapter 1, § 4.1.5). The State Fire Marshal's Quality Assurance Program page says the same: "within 30 days of completing an inspection".
- The form: the state's Fire Protection System(s) Annual Certificate of Inspection (PDF), updated 4/23/24.
Where to send it
Routing depends on where the building is. Regulation 703, Chapter 4, § 8.1.1 says certificates for systems in the area of a Jurisdictional Assistant State Fire Marshal go to that office, with fees if applicable. The State Fire Marshal's "Map It Before You Mail It" notice (PDF) says:
- Look up the property address in the official mapping tool before every submission.
- Dover, Wilmington, Newark and New Castle go to the City Fire Marshal.
- Sort the certificates by county and include a separate check or money order for each county.
Section 8.1 says the certificate goes "along with the appropriate fees". The pages above do not state the fee amount; ask the office that receives the certificate.
Field-by-field notes
The field names below are the ones printed on the state form.
- Owner of the property: name and address of the owner, which may differ from the building address.
- Building/Facility: the building name and street address. Use the same address you looked up on the map, so the routing matches.
- Tenant / Occupant: name, phone, address and an on-site contact.
- Type of report: tick "Annual Certificate of Inspection" for the yearly filing. The other box, "Report of a MAJOR deficiency (other than Annual Inspection)", is for a major deficiency found outside the annual visit.
- Date of inspection: the date the annual inspection was completed. The 30-day clock starts here.
- Licensed Company Name and License #: your company and its state license number.
- Inspector's Name and Certificate # (WBC): the form marks this line "for Water-Based systems". For a fire alarm only report, follow the office's instructions for this line.
- System type: tick "Fire Alarm". The same form covers sprinkler, standpipe, special hazard and cooking systems.
- System ID and System Location: identify the one system this certificate covers. A building with two separate fire alarm systems needs two certificates (§ 8.2).
- Major deficiencies identified during inspection? Tick Yes or No. If Yes, describe them in the comments box.
- Comments/Deficiency description: list each deficiency and the corrective action taken, if any, as § 8.1 requires.
Also keep a copy: § 4.1.5 of Chapter 1 says a Certificate of Inspection is also completed after each periodic inspection, test or maintenance and kept on site as part of the permanent system record.
Major deficiencies: report and repair
- Report when found: a major deficiency is reported to the Office of the State Fire Marshal within one business day, on the form the office prescribes (Chapter 1, § 4.1.6.1). The map notice says "Report major deficiencies within 24 hours" and gives the address QAP.Techservices@delaware.gov.
- Report when repaired: when the major deficiency is repaired, that is also reported within one business day (§ 4.1.6.2). For fire alarms the state has a Fire Alarm System Deficiency Repair Form (PDF), sent with its "Email Form" button.
- Repair deadline: the sections linked here set no fixed number of days to complete a fire alarm repair. The one-business-day rule is for reporting. Ask the State Fire Marshal's office if a deadline applies to your case.
The repair form lists these major deficiency codes:
- 7601 System Out-of-Service / Impaired
- 7602 Unprotected Residential Corridors
- 7603 FACP in ALARM / TROUBLE
- 7604 System Monitoring Out-of-Service
- 7605 More than 10% of Initiating Devices Failed
- 7606 More than 10% of Sounding Devices Failed
- 7607 Other (Make Comment)
Checklist
- One certificate for each fire alarm signaling system.
- Inspection date filled in; certificate sent within 30 days of it.
- Owner, building, tenant, company and license number filled in.
- System ID and location match the system you inspected.
- Major deficiency box ticked; each deficiency and corrective action described.
- Any major deficiency reported within one business day, and its repair reported within one business day.
- Address checked on the official map; sent to the right state, county or city office.
- Certificates sorted by county, with a separate check or money order per county.
- A copy kept on site with the system record.
Sources
- Delaware State Fire Marshal: Quality Assurance Program
- Annual Certificate of Inspection form (PDF)
- Fire Alarm System Deficiency Repair Form (PDF)
- Map It Before You Mail It notice (PDF)
- 1 Del. Admin. Code 703, Chapter 1, § 4.0
- 1 Del. Admin. Code 703, Chapter 4, § 8.0
We are building AlarmCert DE, in development with a founding-member list: it fills this form from your visit data and tracks open deficiencies.